Anhuang specialized in T Cable Connector, we supply high quality T Cable Connector.
35kV 630A T Cable Connector provides a fully screened and fully submersible connection when mated with the proper bushing or plug. For connection of polymeric cable to transformers, switch gear, motors, and other equipment with a remolded separable connector. Optional capacitance test point allows for an easy check of the circuit status or installation of a fault indicator. These 36kV 630A T Cable Connector are made by EPDM with the good quality.
● Deadbreak T Body
● Insulation
● Conductor cable lug
● Adaptor
● Two head screw
● Clearing Paper
● Silicone Lubricant
● Installation Instruction Sheet
● Quality Certificate

1、Semi-conductive EPDM and controls electrical stresses at nose of mating load break product.
2、EPDM INSULATION: High quality sulfur cured EPDM insulation is mixed and formulated in-house for complete control of insulating rubber characteristics.
3、SEMI-CONDUCTIVE INSERT: Molded EPDM conducting rubber screen controls electrical stress.
4、GROUNDING EYE: Molded into the external screen for connection of an earthing wire.
5、STRESS RELIEF: The configuration of the outer screen and the cable adapter provide cable stress relief.
6、CONDUCTOR CABLELUG: Aluminum compression connector is sized to ensure a cool running connector with maximum current transfer.
7、INSULATING PLUG: Molded epoxy insulating plug provides excellent electrical, thermal and mechanical reliability.
8、TWO HEAD SCREW: To make sure have a good contact with the apparatus bushing. SEMI-CONDUCTIVE SHIELD INSERT: Semi-conductive insert is molded of semi
| Reference No. | Conductor Cross Section(mm²) | stretch range over insulation(mm) |
| AH HJ-24/630-50 | 50 | 31 |
| AH HJ-24/630-70 | 70 | 32.6 |
| AH HJ-24/630-95 | 95 | 34.2 |
| AH HJ-24/630-120 | 120 | 35.6 |
| AH HJ-24/630-150 | 150 | 37.2 |
| AH HJ-24/630-185 | 185 | 38.7 |
| AH HJ-24/630-240 | 240 | 41.1 |
| AH HJ-24/630-300 | 300 | 43.2 |
| AH HJ-24/630-400 | 400 | 46.4 |
| AH HJ-24/630-500 | 500 | 49.2 |
| Current Rating | A |
| Continuous nominal current | 630A |
| 24 hours overload | 1000A |
| 27kA/3s | |
| Dynamic short circuit | 40kA/0.2s |
| Description | Parameters (kV) |
| Continuous operating voltage | 35 |
| Maximum Rating Phase-to-Phase | 40.5 |
| Maximum Rating Phase-to-ground | 26 |
| AC withstand voltage ,5min | 117 |
| DC withstand voltage, 15min | 104 |
| Impulse withstand voltage | 200 |
| Minimum Corona Voltage Level | 26 |